LMTD heat exchanger calculator
Duty, LMTD and required area for a counterflow water-to-water exchanger, with area against U.
Free. You get your own copy of this worksheet to change and extend (sign-in required).
Short answer
How do you size a heat exchanger with the LMTD method?
Find the duty Q = ṁ·cp·ΔT, then the log mean temperature difference LMTD = (ΔT₁ − ΔT₂) / ln(ΔT₁/ΔT₂), then the area A = Q / (U·LMTD). Hot water at 0.4 kg/s cooled from 90 °C to 60 °C gives Q = 50.2 kW. Heating cold water from 20 °C to 45 °C in counterflow, the end differences are 45 K and 40 K, so LMTD = 42.5 K. At U = 850 W/(m²·K) the exchanger needs 1.39 m².
The worksheet
Every value below is the output of the Calcanvas compute engine for exactly these cells, evaluated top to bottom. Variables carry their units from one cell to the next.
1. Heat duty
The hot stream cools by 30 K. Temperature differences go in as kelvin (a 30 K drop is the same as 30 °C). The same duty heats the cold stream by 25 K, which sets its flow rate.
mdot = 0.4 kg/scp = 4.18 kJ/(kg*K)Q = (mdot*cp*30 K).to(kW)mc = (Q/(cp*25 K)).to(kg/s)2. Log mean temperature difference
In counterflow, ΔT₁ = 90 − 45 °C at the hot inlet end and ΔT₂ = 60 − 20 °C at the other. When the two are close, LMTD is close to their average.
dT1 = 45 KdT2 = 40 KLMTD = (dT1 - dT2)/ln(dT1/dT2)3. Required area
850 W/(m²·K) is a mid-range overall coefficient for a clean water-to-water plate or shell-and-tube unit. Fouling lowers it, so designers add margin.
U = 850 W/(m^2*K)Area = (Q/(U*LMTD)).to(m^2)areaf(u) = (Q/(u*LMTD)).to(m^2)Us = (300, 350 .. 1500) * W/(m^2*K)Make it yours
Open this example as a board and try a few changes. Results update as you type:
- Make it parallel flow: dT1 = 70 K and dT2 = 15 K, and watch the area grow.
- Add 20% fouling margin with Area*1.2.
- Change the hot flow to 0.6 kg/s and follow the duty through.