Three-phase power calculator
Real, apparent and reactive power of a 400 V, 32 A three-phase load, and the current a 15 kW motor draws.
Free. You get your own copy of this worksheet to change and extend (sign-in required).
Short answer
How do you calculate three-phase power?
Three-phase real power is P = √3 × V × I × pf, with V the line-to-line voltage. At 400 V, 32 A and a power factor of 0.85 that comes to 18.8 kW. The apparent power is 22.2 kVA and the reactive power 11.7 kvar. Run the other way, a 15 kW load at the same voltage and power factor draws 25.5 A per line.
The worksheet
Every value below is the output of the Calcanvas compute engine for exactly these cells, evaluated top to bottom. Variables carry their units from one cell to the next.
1. Supply and load
Line-to-line voltage, line current and power factor. The power factor is a plain number.
V_LL = 400 VI_line = 32 Apf = 0.852. Real, apparent and reactive power
The √3 comes from the 120° shift between phases. Reactive power is the third side of the power triangle, shown in kvar.
P_real = (sqrt(3)*V_LL*I_line*pf).to(kW)S_app = (sqrt(3)*V_LL*I_line).to(kVA)Q_react = sqrt(S_app^2 - P_real^2).to(kvar)3. Current from a motor rating
The same formula rearranged, which is how cables and breakers get sized from a nameplate.
P_motor = 15 kWI_motor = (P_motor/(sqrt(3)*V_LL*pf)).to(A)Make it yours
Open this example as a board and try a few changes. Results update as you type:
- Set V_LL = 480 V for a North American supply.
- Drop pf to 0.7 and watch I_motor go up.
- Change I_line to 63 A to check a bigger feeder.