Cable voltage drop calculator

Drop along 30 m of 2.5 mm² copper at 16 A on 230 V, hot and cold, and the smallest cable that keeps it under 3%.

Free. You get your own copy of this worksheet to change and extend (sign-in required).

Short answer

How do you calculate voltage drop in a cable?

For a single-phase circuit, ΔV = 2·ρ·L·I / S, where the 2 counts the outgoing and return conductor. A 30 m run of 2.5 mm² copper (ρ = 0.0175 Ω·mm²/m) carrying 16 A drops 6.72 V, 2.9% of 230 V. At a conductor temperature of 70 °C copper's resistance is about 20% higher, and the drop rises to 8.0 V (3.5%). Common limits are 3% for lighting and 5% for other loads (IEC 60364), and the NEC suggests 3% for a branch circuit.

The worksheet

Every value below is the output of the Calcanvas compute engine for exactly these cells, evaluated top to bottom. Variables carry their units from one cell to the next.

1. Circuit

Supply voltage, load current, one-way cable length, copper resistivity at 20 °C (1.75×10⁻⁸ Ω·m is 0.0175 Ω·mm²/m) and the conductor cross-section.

ƒx
Vs = 230 V= 230 V
ƒx
I = 16 A= 16 A
ƒx
len = 30 m= 30 m
ƒx
rcu = 1.75e-8 ohm*m= 1.75×10⁻⁸ Ω·m
ƒx
S = 2.5 mm^2= 2.5 mm²

2. Voltage drop

Ω·m times m times A over mm² is volts. The percentage is a plain number.

ƒx
Vd = (2*rcu*len*I/S).to(V)= 6.72 V
ƒx
pct = Vd/Vs*100= 2.92174

3. Hot conductor and cable sizing

Copper's resistance rises about 0.393% per kelvin, so a cable running at 70 °C drops more than the cold figure. The last cells size the cable for a 3% limit and show a balanced three-phase run, where √3 replaces the 2.

ƒx
rhot = rcu*(1 + 0.00393/K * 50 K)= 2.09388×10⁻⁸ Ω·m
ƒx
Vdhot = (2*rhot*len*I/S).to(V)= 8.04048 V
ƒx
Smin = (2*rcu*len*I/(0.03*Vs)).to(mm^2)= 2.43478 mm²
ƒx
Vd3 = (sqrt(3)*rcu*len*I/S).to(V)= 5.81969 V

4. Drop against cable length

The drop grows in a straight line with length, so doubling the run doubles the drop.

ƒx
drop(x) = (2*rcu*x*I/S).to(V)= drop(x)
ƒx
lens = (0, 5 .. 100) * m= [0 m, 5 m, 10 m, 15 m, 20 m, 25 m, 30 m, 35 m, …]
📈 Voltage drop against length
05101520020406080100lens (m)V
drop(lens) — Voltage drop (V) against one-way cable length (m).

Make it yours

Open this example as a board and try a few changes. Results update as you type:

  • Try aluminium: rcu = 2.82e-8 ohm*m.
  • Change S to 4 mm^2 and check the hot drop again.
  • Set Vs = 120 V for a North American circuit and see the percentage jump.

More examples