Thermal expansion calculator
Growth of a 25 m steel pipe heated by 40 K, the stress and force if it is held, and the same pipe in aluminium.
Free. You get your own copy of this worksheet to change and extend (sign-in required).
Short answer
How do you calculate thermal expansion of a pipe or beam?
Linear expansion is ΔL = α·L·ΔT. A 25 m steel pipe (α = 12×10⁻⁶ /K) heated by 40 K grows 12 mm; in aluminium (α = 23×10⁻⁶ /K) it grows 23 mm. If the ends are fixed, the steel instead carries a stress σ = E·α·ΔT = 96 N/mm², a 288 kN push on a 3,000 mm² cross-section. That is why long runs get expansion loops or joints.
The worksheet
Every value below is the output of the Calcanvas compute engine for exactly these cells, evaluated top to bottom. Variables carry their units from one cell to the next.
1. Free expansion
α is per kelvin, so α·L·ΔT is a length. 12×10⁻⁶ /K is a typical figure for carbon steel.
alpha = 12e-6 / KL0 = 25 mdT = 40 KdL = (alpha*L0*dT).to(mm)2. If the pipe can't move
A fully restrained member takes the strain as stress. The length drops out: a 1 m pipe and a 100 m pipe see the same stress.
E = 200000 N/mm^2sigma = (E*alpha*dT).to(N/mm^2)Ap = 3000 mm^2F = (sigma*Ap).to(kN)3. Aluminium and growth against temperature
Aluminium expands about twice as much as steel for the same temperature rise.
alu = 23e-6 / K(alu*L0*dT).to(mm)grow(t) = (alpha*L0*t).to(mm)dts = (0, 5 .. 80) * KMake it yours
Open this example as a board and try a few changes. Results update as you type:
- Try stainless steel at alpha = 17e-6 / K.
- Find the gap a 12 m rail needs for a 50 K swing.
- Give the length in feet (L0 = 80 ft) and read dL in inches.